ASENSE-R-LCD-REL

해외배송

Carbon Dioxide Sensor, Room Mount, 0-2000 ppm, Relay and Temperature, LCD, 0-10VDC & 4-20mA

판매 가격
가격 문의
수량

재고: 0개국내 재고가 없어도 주문 가능합니다. 주문 시 해외 재고를 확인합니다.

무료 배송 10만원 이상

납기: 4 weeks리드타임은 상황에 따라 달라질 수 있습니다.

연구비카드 사용가능
실시간 문의하기
제품 사양
Accuracy:± 30 ppm, ±3 %
Accuracy Detail:Extended Range Accuracy > 2,000 PPM: +/- 30 ppm and +/- 5% of reading; Accuracy is defined after minimum three (3) ABC periods (1 period = 8 days) of continuous operations
Applications:Air and HVAC, Building and Maintenance
Approvals:EMC Directive 2014/30/EC, RoHS Directive 2011/65/EU & RoHS 3 Directive 2015/863/EU
Calibration:Senseair ABC algorithm (Automatic Baseline Correction)
Calibration Note:Calibration 3: Senseair ABC algorithm (Automatic Baseline Correction)
CO2 Measurement Range:0 to 2000 PPM
Deadband:100 ppm
Diagnostics:Complete function check, yellow LED; LCD error indication (display model only)
Electrical Connection:Screw Terminal
Electrical Output:0 to 20 mA, 4 to 20 mA, 0 to 10 Vdc, 2 to 10 Vdc
Enclosure Material:Polycarbonate/ABS Blend, UL94V-1
Enclosure Material Note:ABS, Flammability Rating UL94-HB
Installation:4-6’ o the floor
Material Construction Option:none
Measuring Range:7500 sq. ft. maximum
Operating Humidity:0 to 85% RH, non-condensing
Operating Temperature, Max:122 °F
Operating Temperature, Min:32 °F
Output Detail:Output 1 (CO2): 0/2 to 10V, 0/4 to 20 mA, 0 to 2000 ppm Output 2 (Temperature): 0/2 to 10V, 0/4 to 20 mA, 32 to 122ºF (0 to 50ºC)
Power Consumption:1 W
Relay Output:0.5 A @ 125 Vac; 1 A @ 24 Vdc
Repeatability:±20 ppm ±1% of measured value
Response Time:<10 seconds @ 30 cc / minimum flow rate, <3 minutes diffusion time
Sensor Life:>15 years
Sensor Type:Single beam infrared sensing technology (NDIR)
Series ID:Asense-Room
Storage Temperature, Max:158 °F
Storage Temperature, Min:-40 °F
Supply Voltage:19 to 29 Vac/Vdc
Temperature Measurement Range:-4 to 140ºF
Trip Point Note:1000 ppm (factory set)
Zero Drift:± 0.3 %