DwyerOmegaCN76000-Series
CN76060-PV
1/16 DIN Autotune Controller
- 판매 가격
- 가격 문의
수량
재고: 0개국내 재고가 없어도 주문 가능합니다. 주문 시 해외 재고를 확인합니다.
무료 배송 10만원 이상
납기: 34 weeks리드타임은 상황에 따라 달라질 수 있습니다.
연구비카드 사용가능
실시간 문의하기제품 사양
Accuracy:± 0.25 %FS + 1 digits
Alarm Note:2 alarms operate the same relay; 3.0 A resistive 250 Vac; form A contact (SPST); field programmable for absolute (non-tracking) or deviation (tracking); can be set anywhere within the scaling of the controller; selectable inhibit and power interrupt; automatic/manual reset
Common Mode Rejection:140 dB minimum at 60 Hz
Control Characteristics:Control Action: Reverse (heat) or direct (cool) action; selectable for single or dual setpoint models; Control Modes: Time-proportioning and proportional control modes; selectable preset tune, autotune or manual PID, P, PI or PD with reset anti-windup; Proportional Band : 6 to 5000°F or equivalent °C units; 6 to 9990 for voltage/current inputs; Integral Time : 0.1 to 99.9 minutes, or off ; Derivative Time: 0.01 to 99.99 minutes, or off ; Cycle Time: 2 to 80 s ; Approach Rate: Off to 99.99 min ; On-Off Control: Adjustable on-off differential 2° to full scale in 1° steps, 2 counts to full scale in 1-count steps (voltage/current inputs) ; Ramp and Soak: One ramp time and soak time each adjustable from 0 to 100 hours; end procedure can be set for HOLD or OFF
Cutout Dimensions:45 x 45 mm
Display Type:4 Digit LED
Enclosure Ratings:NEMA Type 12, NEMA Type 2, NEMA Type 3R
Height:48 in
Impedance Input:3 MΩ min, thermocouple; 200 µA, RTD current; 249 Ω, current; 5 kΩ, voltage
Input Type:Thermocouple, RTD, Voltage, Current
Isolation:Relay and SSR outputs are isolated; current, voltage and logic outputs must not share
Length:125 in
Memory:Non-volatile; no batteries required
Normal Mode Rejection:65 dB typical, 60 dB at 60 Hz
Operating Humidity:0 to 90% RH, non-condensing
Operating Temperature, Max:55 °C
Operating Temperature, Min:-10 °C
Power Consumption:5 VA
Protection:Loop Break Protection: Error message is initiated on shorted sensor or open heater circuit; break time adjustable from off to 99 minutes; Loop Break Alarm: On alarm relay equipped units, unit can be programmed to alarm on loop break
Sensor Break Protection:De-energizes control outputs to protect system
Series ID:CN76000-Series
Set Point Adjustment:Selectable
Stability:Line Voltage Stability: ±0.05% over supply voltage range; Temperature Stability: 4 µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV/°F) maximum
Storage Temperature, Max:80 °C
Storage Temperature, Min:-40 °C
Supply Power Type:AC/DC
Supply Voltage:100 to 240 Vac, 132 to 240 Vdc
Weight:227 g