DwyerOmegaACI-CO2-Duct
A/CO2-DUCT-C
Carbon Dioxide Sensor, Duct, 0-2000ppm (0-5V, 0-10V, or 4-20mA), w/Conduit Adaptor
- 판매 가격
- 가격 문의
수량
재고: 0개국내 재고가 없어도 주문 가능합니다. 주문 시 해외 재고를 확인합니다.
무료 배송 10만원 이상
납기: 7 weeks리드타임은 상황에 따라 달라질 수 있습니다.
연구비카드 사용가능
실시간 문의하기제품 사양
Accuracy:± 40 ppm, ±3 %
Applications:Air and HVAC, Building and Maintenance
Approvals:EMC Directive 2014/30/EC
Calibration:Automatic Baseline Correction
CO2 Measurement Range:Up to 10,000 ppm
Contact Fail-Safe:Polarity protected
Dimensions Note:Product Dimensions (H) 5.59" (142 mm) x (W) 3.31" (84 mm) x (D) 1.81" (46 mm)
Display Type:N/A
Electrical Output:4 to 20 mA, 0 to 5 Vdc, 0 to 10 Vdc
Enclosure Material:ABS Plastic
Enclosure Material Note:Duct Box: IP65 rated, PC & ABS blend, Flammability Rating UL94V-0 Cover: Makrolon® 6555 plastic, Flammability Rating UL94V-0 Pipe: PC & ABS blend, Flammability Rating UL94V-0
Enclosure Ratings:IP65, UL94-HB
Gas Concentration:0 to 2000 ppm
Height:4.5 in
Length:1.12 in
Loop Resistance, Max:500 Ohm load maximum
Material Construction Option:none
Measurement Type:Carbon Dioxide
Measuring Range:0 to 2,000 ppm
Mounting Orientation:Duct Mount
Operating Humidity:0 to 95% RH, non-condensing
Operating Temperature, Max:122 °F
Operating Temperature, Min:32 °F
Power Consumption:3 VA
Pressure Dependence:+ 1.6% reading per kPa (deviation from standard pressure 101.3 kPa)
Response Time:≤ 2 minutes, diffusion
Sensor Type:Single beam infrared sensing technology (NDIR)
Series ID:ACI-CO2-Duct
Supply Voltage:19 to 29 Vac
Tightening Torque:0.5 Nm (minimum); 0.6 Nm (maximum)
Warm Up Time:< 1 Minute (@ full specs < 15 minutes)
Weight:0.23 lb
Width:2.75 in